3RU61/3RU51 Thermal Overload Relays
Keywords:
Keywords:
3RU61/3RU51 Thermal Overload Relays
Tel:
3RU61/3RU51 Thermal Overload Relays
Application: The 3RU61/3RU51 thermal overload relays can be used for the protection of three-phase and single-phase AC or DC motors. If using the 3RU61/3RU51 thermal overload relay to protect a single-phase AC or DC load, three poles must be connected in series.
Ambient Temperature: According to IEC 60947-4-1, the 3RU61 thermal overload relay has compensation function in the temperature range of -40 to +60 ºC, and the 3RU51 thermal overload relay is -20 to 60 ºC.
Tripping Class: The 3RU61/3RU51 thermal overload relays are for CLASS 10 normal starting conditions.
Tripping Type: Overload and phase failure
Reset Type: Manual and automatic reset
Reset Time: Depends on the magnitude and characteristics of the tripping current
Ambient Temperature: Storage/Transportation -55 ... +80ºC, temperature compensated to 60ºC
Permitted Rated Current: Control cabinet internal temperature 60 ºC, 100% (above +60 ºC requires derating); Control cabinet internal temperature 70 ºC, 87%