3RU5 Thermal Overload Relay
Keywords:
西门子
热过载继电器
3RU5
SIEMENS
Keywords:
3RU5 Thermal Overload Relay
Tel:
3RU5 Thermal Overload Relay
Applications: Can be used for the protection of three-phase and single-phase AC motors. For the protection of single-phase AC or DC loads, three poles must be used in series.
Ambient temperature: 3RU5156 has temperature compensation in the range of -25ºC to +55ºC. 3RU5166/3RU5176 has temperature compensation in the range of -20ºC to +60ºC.
Tripping rating: Class 10
Tripping characteristic curve: At operating temperature, the tripping time will be reduced by about 25%.
Tripping type: Tripping type
Reset type: Manual and automatic reset, the reset time depends on the tripping current size and characteristics.
Protection rating compliant with IEC60529 standard: IP00 ( open ), IP20 (with terminal cover)
Finger protection compliant with IEC61140 standard: Finger safety (with terminal cover)
Impact resistance compliant with IEC60068-2-27 standard: 8/10g/ms
Altitude: Up to 2000m
Main Circuit
Rated insulation voltage Ui (Pollution degree 3 ):1000V
Rated insulation voltage Ui (Pollution degree 3 ):1000V
Rated impulse withstand voltage Uimp :8 KV
Rated operating voltage Ue :1000V
Current type AC available, frequency up to 400Hz
Safety insulation between main and auxiliary circuits Compliant with IEC60947-1 standard: 1000V
Auxiliary circuit
Number of normally open contacts: 1
Number of normally closed contacts: 1
Auxiliary contact allocation: 1 NO Provides a "tripping" signal, 1 NC Used to disconnect the contactor
Rated insulation voltage Ui (Pollution degree 3 ):690V
Rated impulse withstand voltage Uimp:8 kV
Safety isolation between main and auxiliary circuits: Safety isolation between main and auxiliary circuits: ≥ 440V
Auxiliary circuit wire cross-sectional area
Screw terminals Connection screws: M3, 2 No. Phillips screwdriver
Tightening torque: 0.8 ... 1.2Nm
Conductor cross-sectional area: 1 or 2 core wires, solid wires 2 ×( 0.5 ... 1.5 )mm², 2 ×( 0.75 ... 2.5 )mm² ; Pre-fabricated terminal fine stranded wires 2 ×( 0.5 ... 1.5 )mm², 2 ×( 0.75 ... 2.5 )mm²; AWG guide wire, solid or stranded wire 2 ×( 20 ... 16 ) AWG ,2 ×( 18 ... 14 ) AWG